Prosurge Electronics Co., Ltd

Surge Protection Device,Surge Arrester,Surge Suppressor,TVSS,SPD, Manufacturer and Supplier - China(CN)

Information for Buyers

Prosurge Electronics Co., Ltd
  • Target Markets: All over the world
  • Business Type: Manufacturer
  • Established date: 2006
ETL Listed Type 1 Surge Protection device with SCCR 200kA

ETL Listed Type 1 Surge Protection device with SCCR 200kA

Business Information

  • Min. Order : 50pcs
  • Certificate : CE,,,,,,,RoHS,UL,
  • FOB Port : Guangzhou, China
  • Made In : China(CN)
  • Packaging : Carton
  • Delivery Time : 15~25 days
Favorites
  • ETL Listed Type 1 Surge Protection device with SCCR 200kA

Product Features

Type 1 surge protective device especially designed for low-voltage power supply system at the boundaries from lightning protection zone 1-2 and higher.

1. UL for type 1CA, passed intermediate current 100A, 500A, 1000A and short circuit current rating (SCCR) 200kA without external fuse or circuit breaker.
2. ETL certified surge protector according to UL1449-4th
3. Pluggable design with window fault indication
4. Nominal discharge current In 20kA 8/20 per pole, max discharge current Imax 50kA 8/20 per pole
5. High reliability due to global patented thermally protected MOV (TMOV) with special arc-extinguish device

Technical Data:

 

Part No.

DS50/275-(V+T)(-S)

In accordance with

UL1449-4th

Category IEC/VDE

Type1CA

Max. continuous operating voltage (MCOV)

L – N

(VAC/VDC)

275

/370

N–PE(VAC)

255

Nominal discharge current(8/20) In

L–N

20kA

N-PE

20kA

Max. discharge current(8/20) Imax

L-N

50kA

N-PE

50kA

Voltage protection rating

VPR(L-N)

<1.0kV

VPR(N-PE)

<1.5kV

Response time

L-N

≤25 ns

N-PE

100 ns

Follow current

L-N

No

N-PE

100Arms@Uc

Backup fuse(only required if not already provided in mains)

125A gL/gG

Operating temperature range

- 40ºC ~ + 80ºC

Cross-section of connection wire

Single-strand 35mm2; multi-strand 25mm2

Mounting

35mm DIN-rail in accordance with EN 50022/DIN46277-3

Enclosure material

thermoplastic; extinguishing degree UL94 V-0

Degree of protection

IP20

Installation width

2 modules, DIN 43880

Thermal disconnector

Internal  green – normal ; red - failure

Remote alarm contact

Optional

SCCR rating

200kA

Approvals, Certifications

ETL/CE

Additional data for Remote Alarm Contacts

Remote alarm contact type

Isolated Form C

Switching capability Un/In

AC: 250V/0.5A     DC: 250V/0.1A; 125V/0.2A; 75V/0.5A

Max. Size of connecting wire

Max. 1.5mm2(or # 16AWG)

Product Specifications